XR5FC/XR5SL Installation Guide
6.6 XR5FC and XR5SL power requirements
During AC power failure, the XR5FC and XR5SL panels, and all auxiliary devices connected to the panels, draw
their power from the battery. All devices must be taken into consideration when calculating the battery standby
capacity. Below is a list of the power requirements of the XR5FC and XR5SL panels. Add the additional current
draw of Security Command keypads, smoke detectors, and any other auxiliary devices used in the system for
the total current required.
XR5FC and XR5SL STANDBY BATTERY POWER CALCULATIONS
Standby Current Alarm Current
XR5FC/XR5SL Panels 50mA ______ mA 50mA ______ mA
Relay Outputs 1 and 2 (ON) Qty _____ x 30mA ______ mA Qty _____ x 30mA ______ mA
Active Zone 1 Qty _____ x 3.3mA ______ mA Qty _____ x 3.3mA ______ mA
Active Zones 2 to 5 Qty _____ x 4mA ______ mA 30mA ______ mA
2-Wire Smokes Qty _____ x .1mA ______ mA Qty _____ x .1mA ______ mA
Bell Output (XR5F only) 1500mA max. ______ mA
670, 770, and 771 Keypads Qty _____ x 125mA ______ mA Qty _____ x 125mA ______ mA
Annunciator (On) Qty _____ x 20mA ______ mA
690 & 790 Keypads (annunciator on or off) Qty _____ x 100mA ______ mA Qty _____ x 100mA ______ mA
692F Keypad Qty _____ x 30mA ______ mA Qty _____ x 30mA ______ mA
Annunciator (On) Qty _____ x 10mA ______ mA
Auxiliary Powered Devices on
Terminals 7 and 11 ______ mA ______ mA
(Other than keypads)
Total Standby ___________ mA Total Alarm ____________ mA
Total Standby ____________ mA x number of standby hours needed ______ = ___________ mA/hours
Total Alarm + ___________ mA/hours
Total ___________ mA/hours
x_.001_____
= ___________ A/hours required
Bell Output
7.1 Terminal 5 (XR5FC Only)
Terminal 5 supplies 12 VDC Bell Output to power alarm bells or horns. The output is rated for a maximum of 1.5
Amps. This output can be steady or pulsed depending upon the Bell Action specified in Output Options
programming. Terminal 10 is the ground reference for terminal 5.
4-Wire Smoke Detector Power
8.1 Terminal 6 (XR5FC Only)
Terminal 6 provides up to 100mA at 12 VDC to power 4-wire smoke detectors or other auxiliary powered
devices. This output can be turned off by the user for 5 seconds using the Sensor Reset User Menu option.
Terminal 10 is the ground reference for terminal 6.
* Based on 10% of active zones in alarm condition